California General Electrician/Cheat sheet
California General Electrician cheat sheet: key rules and summary
100 multiple-choice questions; 4.5 hours; open book (NEC + Title 8); 70% passing score; California DIR/DLSE.
- 20 numbers
- 4 sections
- 4 rules people get wrong
Memorise these first
- 14 AWG copperMaximum 15A branch circuit overcurrent protection rating (75°C THHN)
- 3 feet (36 inches)Minimum depth of working space in front of 0-150V equipment (Condition 1, 2, or 3)
- 2.00 cu. in.Volume allowance per 14 AWG conductor in an outlet/device box
Conductor ampacity & sizing (NEC 310.16)
- 14 AWG copper
- Maximum 15A branch circuit overcurrent protection rating (75°C THHN)NEC 240.4(D)(3)
- 12 AWG copper
- Maximum 20A branch circuit overcurrent protection rating (75°C THHN)NEC 240.4(D)(5)
- 10 AWG copper
- Maximum 30A branch circuit overcurrent protection rating (75°C THHN)NEC 240.4(D)(7)
- 8 AWG copper
- 50A ampacity at 75°C copper; 55A at 90°CNEC Table 310.16
- 125% continuous
- Conductor sizing multiplier for continuous loads (running 3+ continuous hours)NEC 210.19(A)(1)
Working spaces & clearances (NEC 110.26)
- 3 feet (36 inches)
- Minimum depth of working space in front of 0-150V equipment (Condition 1, 2, or 3)NEC Table 110.26(A)(1)
- 30 inches or width
- Minimum width of working space in front of electrical equipment (whichever is greater)NEC 110.26(A)(2)
- 6.5 feet (78 inches)
- Minimum headroom height of working space around service equipment and panelboardsNEC 110.26(A)(3)
- 90 degrees
- Minimum door opening angle for equipment doors in designated working spacesNEC 110.26(A)(2)
Box fill & conduit calculations
- 2.00 cu. in.
- Volume allowance per 14 AWG conductor in an outlet/device boxNEC Table 314.16(B)
- 2.25 cu. in.
- Volume allowance per 12 AWG conductor in an outlet/device boxNEC Table 314.16(B)
- 2.50 cu. in.
- Volume allowance per 10 AWG conductor in an outlet/device boxNEC Table 314.16(B)
- Double volume (2x)
- Volume allowance for yoke containing standard switches or duplex receptaclesNEC 314.16(B)(4)
- 40% maximum fill
- Maximum permissible conduit cross-sectional fill for 3 or more conductorsNEC Chapter 9 Table 1
- 53% maximum fill
- Maximum permissible conduit cross-sectional fill for a single conductorNEC Chapter 9 Table 1
Grounding & bonding (NEC 250)
- 8 feet minimum
- Minimum length and driven depth of ground rod electrode into the soilNEC 250.52(A)(5)
- 6 feet minimum
- Minimum separation distance between two driven rod, pipe, or plate grounding electrodesNEC 250.53(A)(3)
- 25 ohms or less
- Maximum resistance to ground for a single rod electrode before a supplemental rod is mandatedNEC 250.53(A)(2)
- Table 250.66
- Determines grounding electrode conductor (GEC) size based on service-entrance conductor sizeNEC Table 250.66
- Table 250.122
- Determines equipment grounding conductor (EGC) size based on circuit breaker/fuse ratingNEC Table 250.122
Second read
Rules people get wrong
- Continuous loads must be calculated at 125% of the rating before sizing branch conductors and overcurrent devices (NEC 210.19(A)(1), 215.2).
- Equipment grounding conductor (EGC) size is governed by the upstream fuse/breaker rating (Table 250.122), whereas grounding electrode conductors (GEC) are sized by the incoming service conductors (Table 250.66).
- Kitchen small appliance branch circuits require a minimum of two 20-ampere circuits with 12 AWG copper, not 15A (NEC 210.11(C)(1)).
- Neutral conductor ampacity: in 3-phase 4-wire wye systems supplying nonlinear loads (computers, LED drivers), the neutral carries harmonic currents and counts as a current-carrying conductor for derating (NEC 310.15(E)(3)).